NAPCO Gemini Hybrid control panel 8 to 32/48 zone max Advanced


(SKU# : GEM-P3200)


Napco's Gemini GEM-P3200 a popular, all-around 8 zone hybrid control expandable to 32 zones or 48 wireless points


DESCRIPTIONS

NAPCO’s Gemini GEM-P3200 is a state-of-the-art microcomputer-based burglary and residential fire alarm control panel of modular design. Integrally an 8-zone panel, it will support up to 48 zones with optional zone expansion modules, wireless receiver modules and/or GEM-RP1CAe2/GEM-K1CA Keypads. Each panel includes an integral digital communicator. The control panel features programmable area partitioning. That is, the system may be divided into up to 2 discrete multiple-zone areas, each allowing access by only those users programmed for their respective area(s).

CONTROL PANEL FEATURES

  • 8 End-of-line-resistor burglary zones programmablefor area, exit/entry delay, interior, follower,day zone, chime, fire options, sensor watch,swinger shutdown, zone anding and a variety of other features
  • Up to 48 points of up to 32 zones with optionalzone-expansion modules 4- zone keypad EZMs(built-in)
  • Including up to 2 2-wire fire zones
  • Up to 32 individually coded users, each with aprogrammable authority level
  • 3 on-board relay outputs, expandable 24 externalrelay outputs
  • 3 keypad panics: fire, police & auxiliary
  • 2 independent area partitions
  • Up to 7 separate access stations by up to 32 users
  • Up to 24 separately-addressable X-10 devices withthe GEM-X10KIT
  • English-language prompts & system status messagesfrom choice of keypad (8) models
  • User-customized zone descriptions, reprogrammableas required
  • 2-wire and 4-wire smoke detectors
  • Reports alarms, restores and troubles by zone
  • 255 event schedule
  • 800 event log
  • Overview mode permits monitoring and control oftotal system from one keypad
  • 2 programmable entry delay times
  • Interior-bypass group
  • Dynamic battery test interrupts charging andplaces battery under load every four hours
  • Chime by zone; programmable duration
  • Non-volatile RAM retains memory during powerlosses
  • Quickloader™ programmable
  • Auto-Download Log
  • Exclusive V.A.L.I.D.™ feature (Verifying AutomaticLine Integrity Diagnostic) reduces false alarms dueto changes in line resistance

COMMUNICATOR FEATURES

  • Compatible with all major receiver formats,including BFSK, 4/2, Modem 2, SIA, 4/3/1, 4 + 2Express and Point ID
  • Rotary dial and TouchTone™ with Rotary backup
  • 3 20-digit telephone numbers
  • Backup reporting, double reporting; split reporting
  • 32 User codes with opening/closing reporting byuser
  • AC failure reporting with programmable reportdelay
  • Supervised telephone line cut with programmabledelay
  • Pager capability

SPECIFICATIONS

  • Operating temperature: 0-49°C (32-120°F)
  • Input power: 16.5Vac via Class 2 Plug-In40VA transformer
  • Loop voltage: 10-13Vdc
  • Loop current:2.5mA with 2.2ohm end-of-lineresistor (model EOL2.2K); 5mA for 2-wiresmoke-detector zones
  • Loop resistance: 300W max.; 50W for 2-wiresmoke detector zones
  • Relay outputs (burglary; reset; aux): wet,12Vdc, 1.2A max.; dry (cut related jumper fordry contacts), SPDT contacts 24Vdc, 2A, 0:6 PF
  • Auxiliary power output: 12Vdc regulated
  • Remote power output: 12Vdc regulated (forkeypads)
  • 650 mA combined standby current (remotepower + aux. power + reset relay power)
  • Standby time: residential fire/burglary & commercialburglary, 4 hours min.
  • EZM module: GEM-EZM8: Input, 50mA(including PGM output. PGM output: 5mA,12V special application
  • Keypad current: GEM-RP1CAe2: 100mA;35mA if backlighting is disabled (cut W1,W2 & W3) PGM Output: 5mA, 12V specialapplication
  • Maximum number of keypads: 7. Maximumwiring length for each run (#22AWG): 1000’divided by total number of keypads & EZMson run
  • Designer keypad dimensions: 4 3/8” x 5 7/8”x 1 1/6” (HWD); 11.1cm x 14.9cm x 2.7cm(HWD)

Downloads